Juniper Networks M160 Network Router User Manual


 
M160 Internet Router Hardware Guide
Table 16: Component Power Requirements
Component Power Requirement (Amps)
Base system (cooling system, power supplies, and c raft
interface)
7-1 0 A/48 V
Hostmodule(RoutingEngineandMCS) 1.3A/48V
FPC
2.4A/48V
PCG
0.2A/48V
SFM
1.3A/48V
You can use the information in Table 16 and the M160 Internet Router PIC
Guide to calculate power consumption for various hardware configurations,
input current from a different source voltage, and thermal output, as shown
in the following examples. (For an added safety margin, the examples use
a generalized value for PICs of 0.625 A/48 V each.)
Power consumption for minimum configuration:
Base system + 1 FPC + 1 SFM + 1 host module + 2 PCGs + 4 PICs =
7 A + 2.4 A + 1.3 A + 1.3 A + 2(0.2 A) + 4(0.625 A) =
7 A + 2.4 A + 1.3 A + 1.3 A + 0.4 A + 2.5 A = 14.9 A @ 48 V = 715 W DC
Power consumption for maximum configuration:
Base system + 8 FPCs + 4 SFMs + 2 host modules + 2 PCGs + 32 PICs =
10 A + 8(2.4 A) + 4(1.3 A) + 2(1.3 A) + 2(0.2 A) + 32(0.625 A) =
10A + 19.2A + 5.2A + 2.6A + 0.4A + 20A=57.4A@48V=2755WDC
Input current from a DC source other than 48 V (based on maximum
configuration):
(54 VDC input) x (input current X) = (48 VDC input) x (input current Y)
54 x X = 48 x 57.4 A
X=48 x 57.4A/54=51.0A
System thermal output for maximally configured router:
105% of Watts D C/0.293 = BTU/hr
1.05 x 2755/0.293 = 9873 BTU/hr
NOTE: If you plan to operate a maximally configured router, we recommend that
you provision at least 70 A @ 48 VDC and use a facility circuit breaker rated for
70 A minimum. Doing so enables you to operate the router in any configuration
without upgrading the pow er infrastructure, and allows the router to function at
full capacity using one power supply.
If you plan to operate the router at less than the maximum configuration and do not
provision a 70 A circuit breaker, we recommend that you provision a circuit breaker
rated for at least 125% of the continuous current that the system draw s at 48 V.
66 Power Guidelines, Requirements, and Specifications