Panasonic MDDDT3530 Power Supply User Manual


 
- 20 -
System Configuration and Wiring
List of Available Components
As these models with * are used for both 1-phase 200V and 3-phase 200V, make a choice
according to the power source.
When these wires are used, wire length between circuit breaker and amplifier should be less than 3 m.
The model numbers of circuit breaker and magnetic contactors shown in the above list are manufactured by
Matsushita Electric Works, Ltd.
• Use the circuit breaker as shown in App.3 to meet relevant EC Directives.
The model number of noise filters (options) shown in the above are manufactured by Okaya Electric Industries
Co., Ltd.
<Notes>
• CN POWER, CN MOTOR and earth terminals
Wires should be copper conductors of a temperature rating of 60˚C or above.
Earth wire diameter should be 2.0 mm
2
(AWG14) or larger.
Please also consider the electrochemical potentials between metal conductor including closed loop terminals.
The electrochemical potentials shall be less than 0.6V.
Magnetic contactor
(contacts)
BMFT61041N
(3P+1a)
BMFT61541N
(3P+1a)
BMFT61541N
(3P+1a)
MMFT61042N
(3P+1a)
Noise
filter
DVOP1441
DVOP1442
DVOP1441
DVOP1442
DVOP1441
DVOP1442
Circuit
breaker
(rated current)
BK251
(5A)
BK2101
(10A)
BK351
(5A)
BK3101
(10A)
BK351
(5A)
BK3101(10A)
BK3151
(15A)
Required Power
(at the rated load)
Approx. 0.3kVA
Approx.
0.4kVA
Approx.
0.5kVA
Approx.
1.0kVA
Approx.
0.3kVA
Approx.
0.5kVA
Approx.
0.9kVA
Approx.
0.3kVA
Approx.
0.5kVA
Approx. 0.9kVA
Approx.
1.3kVA
Output
30 ~ 50W
100W
200W
400W
30 ~ 50W
100W
200W
400W
30 ~ 50W
100W
200W
400W
750W
Voltage
1-phase,
100V
*1-phase,
200V
1-phase,
200V
*3-phase,
200V
3-phase,
200V
Main circuit wire diameter
(L1 , L2, L3,
U, V, W, E)
0.75mm
2
~ 0.85mm
2
AWG 18
Series
MUDS
Amplifier