Calibrating I/O
Calibrating Voltage
When calibrating the IOLAN Analog input for voltage, you will need a calibration meter that is better
than .1% volts precision. When you calibrate one channel, all voltage channels are automatically
calibrated for that range; if another channel is set for a different range, you will need to calibrate that
channel separately, but all channels that use that range are also automatically calibrated.
Calibrating Current
When calibrating the IOLAN Analog input for current, you will need a calibration meter that is better
than .1% current precision. Each channel needs to be calibrated individually.