Cabletron Systems 8H02-16 Switch User Manual


 
Installing the 8H02-16
8H02-16 User’s Guide 3-3
3.4.2 Rackmount Installation
To install the 8H02-16 in a 19-inch rack, Cabletron Systems includes an
accessory kit containing the rackmount brackets, mounting screws, and a
strain-relief bracket for cable management.
Tabletop and shelf installations must be within reach of the network
cabling and meet the requirements listed below:
Locate the 8H02-16 within seven feet of an appropriate grounded
power receptacle that meets the power supply requirements listed in
Appendix A, Specifications.
Maintain a temperature of between 5°C (41°F) and 40°C (104°F) at
the installation site with fluctuations of less than 10°C per hour.
WARNING
Before installing the 8H02-16 into a rack, ensure that the rack
supports the device(s) without compromising the stability of the
rack. Otherwise, personal injury and/or equipment damage
may result.
!
CAUTION
To ensure proper ventilation and prevent overheating, leave a
minimum clearance space of 5.1 cm (2.0 in) at the left, right
and rear of the 8H02-16.