HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
Chapter 6 - Parameter Description [FU2]
6-20
This function is used to allow the inverter to reset itself for
a selected number of times after a fault has occurred. The
inverter can restart itself automatically when a fault occurs.
To use the speed search function during auto restarting set
FU2-22 to ‘xx1x’. See FU2-22 ~ FU2-25.
When an under voltage (LV) fault, inverter disable (BX) or
Arm short occurs, the drive does not restart automatically.
Note: Inverter decreases the retry number by one as a fault
occurs. When restarted without a fault during 30 seconds,
the inverter increases the retry number by one.
FU2-28: Speed search hold time
The inverter starts speed search function after the preset
time t1 elapses. Set the desired time for inverter to restart
the previous operation using Speed search function.
Speed search function [FU2-22] is activated automatically
during exchanging function.
Code
Keypad
display
Description
Factory
setting
Setting
Range
FU2-28 SS blk time
Speed search
hold time
during speed
search
1 sec
0 ~ 60
sec
Note: This parameter is not valid when low voltage (LV)
fault or instant power loss (within 15msec) occurs.
FU2-30: Rated Motor Selection
FU2-31: Number of Motor Pole
FU2-32: Rated Motor Slip
FU2-33: Rated Motor Current
FU2-34: No Load Motor Current
FU2-36: Motor Efficiency
FU2-37: Load Inertia
If you do not set these values, inverter will use its default
values.
This parameter sets the motor capacity. Other motor
related parameters are changed automatically according to
Output Frequency
Time
1
st
Fault 2
nd
Fault
Restart with
Speed Search
Restart with
Speed Search
t t
t: FU2-27
Input power[v]
Time [sec]
Motor speed [rpm]
t1
t2 t3
t1 : Ssearch wait time
t2 : Ssearch Accel time
t3 : Ssearch Decel time
Output vtg [V]
Time [sec]
Time [sec]
FU2
Motor select
30 0.75kW
0 30
Factory Default: 0.75 kW 0
(This value is set according to the model number before shipping)
FU2
SS blk time
28 1.0 sec
1.0 28
Factory Default: 1.0 sec 1. 0