HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
5-1
CHAPTER 5 - PARAMETER LIST
5.1 Drive Group [DRV]
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
DRV-00
10
Command Frequency or
Command Torque
(Output Frequency/
Torque during motor run,
Reference Frequency/
Torque during motor
stop)
Output Current (LCD)
Cmd. freq
or
Cmd. Trq
F or r
(DRV-13)
0 to FU1-20 (Max. freq) 0.01 0.00 [Hz] Yes 6-2
DRV-01 Acceleration Time
Acc. time
01 0 to 6000 0.1 10.0 [sec] Yes 6-2
DRV-02 Deceleration Time
Dec. time
02 0 to 6000 0.1 20.0 [sec] Yes 6-2
Keypad 0
Fx/Rx-1 1
DRV-03
Drive Mode
(Run/Stop Method)
Drive mode
03
Fx/Rx-2 2
- Fx/Rx-1 No 6-2
Keypad-1 0
Keypad-2 1
V1 2
I 3
DRV-04
Frequency Mode or
Torque Mode
(Frequency/Torque
setting Method)
Freq mode
or
Torque mode
04
V1+I 4
- Keypad-1 No 6-2
DRV-05 Step Frequency 1
Step freq-1
05 10.00 [Hz]
DRV-06 Step Frequency 2
Step freq-2
06 20.00 [Hz]
DRV-07 Step Frequency 3
Step freq-3
07
FU1-22 to FU1-20
(Starting freq to Max. freq)
0.01
30.00 [Hz]
Yes 6-2
DRV-08 Output Current
Current
08 The Load Current in RMS - [A] - 6-2
DRV-09 Motor Speed
Speed
09 The Motor Speed in rpm - [rpm] - 6-2
DRV-10 DC link Voltage
DC link Vtg
10 The DC Link Voltage inside inverter - [V] - 6-2
DRV-11 User Display Selection
User disp
11 Selected in FU2-73 (User Disp) - - - 6-2
DRV-12 Fault Display
Fault
12 - - -
None
nOn
- 6-2
0 [Forward]
DRV-13 Motor Direction Set
Not
displayed in
LCD keypad
13 Not available
1 [reverse]
- 0 Yes 6-2
DRV-14
Target/Output Frequency
Display
TAR
OUT
14 - - - 0.00 [Hz] Yes 6-2
DRV-15
11
Reference/Feedback
Frequency Display
REF
FBK
15 - - - 0.00 [Hz] Yes 6-2
DRV-16 Speed Unit Selection
Hz/Rpm Disp
16 Hz disp 0 - - Yes 6-2
10
The speed unit is changed to [%] when FU2-39 is set to ‘Sensorless_T’ or ‘Vector_TRQ’.
11
Code DRV-15 appears only when FU2-47 is set to ‘Yes’.