Chapter 5 - Parameter List
5-3
5.2 Function 1 Group [FU1]
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU1-00 Jump to Desired Code #
Jump code
Not displayed 1 to 60 Not available 1 1 Yes 6-2
None 0
Forward Prev 1
FU1-03 Run Prevention
Run Prev.
03
Reverse Prev 2
- None No 6-2
Linear 0
S-curve 1
U-curve 2
Minimum 3
FU1-05 Acceleration Pattern
Acc. pattern
05
Optimum 4
- Linear No 6-2
Linear 0
S-curve 1
U-curve 2
Minimum 3
FU1-06 Deceleration Pattern
Dec. pattern
06
Optimum 4
- Linear No 6-2
Decel 0
DC-brake 1
FU1-07 Stop Mode
Stop mode
07
Free-run 2
- Decel No 6-2
FU1-08
13
DC Injection Braking
Frequency
DcBr freq
08 FU1-22 to 60 [Hz] 0.01 5.00 [Hz] No
FU1-09
DC Injection Braking
On-delay Time
DcBlk time
09 0 to 60 [sec] 0.01 0.1 [sec] No
FU1-10
DC Injection Braking
Voltage
DcBr value
10 0 to 200 [%] 1 50 [%] No
FU1-11
DC Injection Braking
Time
DcBr time
11 0 to 60 [sec] 0.1 1.0 [sec] No
6-2
FU1-12
Starting DC Injection
Braking Voltage
DcSt value
12 0 to 200 [%] 1 50 [%] No
FU1-13
Starting DC Injection
Braking Time
DcSt time
13 0 to 60 [sec] 0.1 0.0 [sec] No
6-2
FU1-14 Pre-excitation Time
PreExTime
14 0 to 60 [sec] 0.1 1.0 [sec] No 6-2
FU1-15 Hold Time
Hold Time
15 0 to 1000 [ms] 1 1000 [ms] No 6-2
FU1-16 Pre-excitation Current
Flux Force
16 100 to 500 [%] 0.1 100.0 [%] No 6-2
FU1-20 Maximum Frequency
Max freq
20 40 to 400 [Hz] 0.01 60.00 [Hz] No
FU1-21 Base Frequency
Base freq
21 30 to FU1-20 0.01 60.00 [Hz] No
FU1-22 Starting Frequency
Start freq
22 0.01 to 60 [Hz] 0.01 0.50 [Hz] No
6-2
No 0
FU1-23 Frequency Limit selection
Freq limit
23
Yes 1
- No No
FU1-24
14
Low Limit Frequency
F-limit Lo
24 FU1-22 to FU1-25 0.01 0.50 [Hz] No
6-2
13
Code FU1-08 through FU1-11 appears only when FU1-07 is set to ‘DC-Brake’.
14