HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
Chapter 5 - Parameter List
5-9
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU2-72 Power On Display
PowerOn disp
72 0 to 12 1 0 Yes 6-2
Voltage 0
FU2-73 User Display Selection
User disp
73
Watt 1
- Voltage Yes 6-2
FU2-74
Gain for Motor Speed
Display
RPM factor
74 1 to 1000 [%] 1 100 [%] Yes 6-2
None 0
Int. DB-R 1
FU2-75
DB (Dynamic Braking)
Resistor Mode Selection
DB mode
75
Ext. DB-R 2
- Int. DB-R Yes 6-2
FU2-76
23
Duty of Dynamic Braking
Resistor
DB %ED
76 0 to 30 [%] 1 10 [%] Yes 6-2
FU2-79 Software Version
S/W version
79 Ver 2.0 - - - 6-2
FU2-81
24
2
nd
Acceleration Time
2nd Acc time
81 0 to 6000 [sec] 0.1 5.0 [sec] Yes
FU2-82 2
nd
Deceleration Time
2nd Dec time
82 0 to 6000 [sec] 0.1 10.0 [sec] Yes
FU2-83 2
nd
Base Frequency
2nd BaseFreq
83 30 to FU1-20 0.01 60.00 [Hz] No
Linear 0
Square 1
FU2-84 2
nd
V/F Pattern
2nd V/F
84
User V/F 2
- Linear No
FU2-85 2
nd
Forward Torque Boost
2nd F-boost
85 0 to 15 [%] 0.1 2.0 [%] No
FU2-86
2
nd
Reverse Torque
Boost
2nd R-boost
86 0 to 15 [%] 0.1 2.0 [%] No
FU2-87 2
nd
Stall Prevention Level
2nd Stall
87 30 to 150 [%] 1 150[ %] No
FU2-88
2
nd
Electronic Thermal
Level for 1 minute
2nd ETH 1min
88 FU2-89 to 200 [%] 1 150 [%] Yes
FU2-89
2
nd
Electronic Thermal
Level for continuous
2nd ETH cont
89
50 to FU2-88
(Maximum 150%)
1 100 [%] Yes
FU2-90 2
nd
Rated Motor Current
2nd R-Curr
90 1 to 200 [A] 0.1 3.6 [A] No
6-2
No 0
FU2-91
Read Parameters into
Keypad from Inverter
Para. Read
91
Yes 1
- No No
No 0
FU2-92
Write Parameters to
Inverter from Keypad
Para. Write
92
Yes 1
- No No
6-2
No 0
All Groups 1
DRV 2
FU1 3
FU2 4
I/O 5
EXT 6
COM 7
FU2-93 Initialize Parameters
Para. Init
93
APP 8
- No No 6-2
23
Code FU2-76 appears only when FU2-75 is set to ‘Ext. DB-R’.
24
Code FU2-81 through FU2-90 appear only when one of I/O-12 ~ I/O-14 is set to ‘2nd function’.