Chapter 6 - Parameter Description [DRV]
6-3
DRV-02: Deceleration Time
The inverter targets the FU2-70 when accelerating or
decelerating. When the FU2-70 is set to “Maximum
Frequency”, the acceleration time is the time taken by the
motor to reach FU1-20 from 0 Hz. The deceleration time is
the time taken by the motor to reach 0 Hz from FU1-20
[Maximum Frequency].
When the FU2-70 is set to ‘Delta Frequency’, the
acceleration and deceleration time is the time taken to
reach a targeted frequency (instead the maximum
frequency) from a frequency.
The acceleration and deceleration time can be changed to
a preset transient time via multi-function inputs. By setting
the multi-function inputs (P1, P2, P3) to ‘XCEL-L’, ‘XCEL-
M’, ‘XCEL-H’ respectively, the Accel and Decel time set in
I/O-25 to I/O-38 are applied according to the binary inputs
of the P1, P2, P3.
Note:
I/O-12 to I/O-14: Sets the terminal function of P1, P2,
P3 terminal inputs.
Code
LCD
display
Description
XCEL-
H
XCEL-
M
XCEL-
L
Factory
setting
DRV-
01
Acc time Acc time 0 0 0 0 10 sec
DRV-
02
Dec time Dec time 0 0 0 0 20 sec
I/O-25 ACC-1 Acc time 1 0 0 1 20 sec
I/O-26 DEC-1 Dec time 1 0 0 1 20 sec
I/O-27 ACC-2 Acc time 2 0 1 0 30 sec
I/O-28 DEC-2 Dec time 2 0 1 0 30 sec
I/O-29 ACC-3 Acc time 3 0 1 1 40 sec
I/O-30 DEC-3 Dec time 3 0 1 1 40 sec
I/O-31 ACC-4 Acc time 4 1 0 0 50 sec
I/O-32 DEC-4 Dec time 4 1 0 0 50 sec
I/O-33 ACC-5 Acc time 5 1 0 1 40 sec
I/O-34 DEC-5 Dec time 5 1 0 1 40 sec
I/O-35 ACC-6 Acc time 6 1 1 0 30 sec
I/O-36 DEC-6 Dec time 6 1 1 0 30 sec
I/O-37 ACC-7 Acc time 7 1 1 1 20 sec
I/O-38 DEC-7 Dec time 7 1 1 1 20 sec
FU2-71 [Accel/Decel time scale]
Set the Accel / Decel time unit.
Setting Unit Description
0 0.01 sec
Minimum 0 sec settable
Maximum 60 sec settable
1 0.1 sec
Minimum 0 sec settable
Maximum 600 sec settable
(Factory setting)
2 1 sec
Minimum 0 sec settable
Maximum 6000 sec settable*
* Up to 6000 sec setting is avaiable via LE-200 keypad.
DRV-03: Drive Mode (Run/Stop Method)
Select the source of run/stop command.
DRV
Dec. time
02 20.0 sec
20.0 02
Factory Default: 20.0 sec 20.0
Related Functions: FU1-20 [Max freq]
FU2-70 [Reference freq. for Accel/Decel]
FU2-71 [Accel/Decel time scale]
I/O-12 to I/O-14 [Multi-function input
terminal P1, P2, P3]
I/O-25 to I/O-38 [Acc/Dec time for step
frequency]
FU2-70: Selects the frequency to be targeted for acceleration
and deceleration. [Max Freq, Delta Freq]
FU2-71: Selects the time scale. [0.01, 0.2, 1]
I/O-12 to I/O-14: Sets the terminal function of P1, P2, P3
terminal inputs.
I/O-25 to I/O-38: Presets the Accel/Decel time activated via
multifunction inputs (P1, P2, P3)
Output Frequency
Max. Freq.
Time
Acc. time Dec. time
DRV
Drive mode
03 Keypad
1 03
Factory Default: Fx/Rx-1 1