HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
Chapter 5 - Parameter List
5-7
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU2-27
Delay Time
Before Auto Restart
Retry Delay
27 0 to 60 [sec] 0.1 1.0 [sec] Yes 6-2
FU2-28 Speed Search Hold Time
SS blk time
28 0 to 60 [sec] 0.1 1.0 [sec] No 6-2
0.75kW 0
1.5kW 1
2.2kW 2
3.7kW 3
5.5kW 4
7.5kW 5
11.0kW 6
15.0kW 7
18.5kW 8
FU2-30 Rated Motor Selection
Motor select
30
22.0kW 9
-
18
No
FU2-31 Number of Motor Poles
Pole number
31 2 to 12 1 4 No
FU2-32 Rated Motor Slip
Rated-Slip
32 0 t o10 [Hz] 0.01 No
FU2-33
Rated Motor Current
(RMS)
Rated-Curr
33 1 to 200 [A] 1 No
FU2-34
No Load Motor Current
(RMS)
Noload-Curr
34 0.5 to 200 [A] 1 No
FU2-36 Motor Efficiency
Efficiency
36 70 to 100 [%] 1
19
No
FU2-37 Load Inertia
Inertia rate
37 0 to 1 1 0 No
6-2
FU2-38 Carrier Frequency
Carrier freq
38 1 to 15 [kHz] 1 5 [kHz] Yes 6-2
V/F 0
Slip comp 1
Sensorless_S 2
Sensorless_T 3
Vector_SPD 4
FU2-39 Control Mode Selection
Control mode
40
Vector_TRQ 5
- V/F No 6-2
No 0
All 1
Rs + Lsigma
Enc Test
FU2-40 Auto Tuning
Auto tuning
41
Tr
- No No
FU2-41
20
Stator Resistance of
Motor
Rs
42 0 to (depending on FU2-30) [ohm] 0.001 No
FU2-42
Leakage Inductance of
Motor
Lsigma
44 0 to (depending on FU2-30) [mH] 0.001
21
No
6-2
18
The rated motor is automatically set according to the inverter model name. If different, set the motor capacity connected.
19
This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value of the motor.
20
Code FU2-41 through FU2-46 appears only when FU2-39 is set to ‘Sensorless_X’ or ‘Vector_XXX’.
21
This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value of the motor.