Chapter 7 - Options
7-21
• DB resistor wiring for 1 – 5 HP Inverter
DB resistor terminal Terminal description
B1, B2 Connect the DB Resistor to Inverter terminal B1,B2.
TH1, TH2
Thermal sensors provided with the DB resistor.
P1 is ON (TH1-TH2 Shorted) at normal (ambient temp) and P1 is OFF (TH1-TH2
Open) at overheated status. Connect the thermal sensor to one of the multi-function
input (P1, P2 or P3, I/O 12-14 setting: Ext Trip-B).
IM
U
V
W
G
R
S
T
B2
DB Resistor
F
X
R
X
B
X
RST
JO
P2
P3
FM
+
FM
5G
A
nalog freq
output
2)
(0-10V)
P1
REV Run / Stop
FWD Run / Stop
Fault reset
Jog
Max Current thru
PC : 5mA
CM
24 V
TH1
TH2
Max distance : 5m
Multi-function input terminal
(I/O-12 Setting : Ext Trip-B)
B2B1
B1