HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
Chapter 5 - Parameter List
5-20
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
APP-02
27
Traverse Amplitude
Trv. Amp
02 0.0 to 20.0 [%] 0.1 0.0 [%] Yes 6-2
APP-03
Traverse Scramble
Amplitude
Trv. Scr
03 0.0 to 50.0 [%] 0.1 0.0 [%] Yes 6-2
APP-04 Traverse Accel Time
Trv Acc Time
04 0 to 6000 [sec] 0.1 2.0 [sec] Yes 6-2
APP-05 Traverse Decel Time
Trv Dec Time
05 0 to 6000 [sec] 0.1 3.0 [sec] Yes 6-2
APP-06
Traverse Offset (Hi)
Setting
Trv Off Hi
06 0.0 to 20.0 [%] 0.1 0.0 [%] Yes 6-2
APP-07
Traverse Offset (Lo)
Setting
Trv Off Lo
07 0.0 to 20.0 [%] 0.1 0.0 [%] Yes 6-2
APP-08
28
Running Auxiliary Motor
Number Display
Aux Mot Run
08 - - - - 6-2
APP-09
Starting Aux. Motor
Selection
Starting Aux
09 1 to 4 1 1 Yes 6-2
APP-10
Operation Time Display
on Auto Change
Auto Op Time
10 - - - - 6-2
APP-11
Start Frequency of Aux.
Motor 1
Start freq 1
11 0 to FU1-20 0.01 49.99 [Hz] Yes
APP-12
Start Frequency of Aux.
Motor 2
Start freq 2
12 0 to FU1-20 0.01 49.99 [Hz] Yes
APP-13
Start Frequency of Aux.
Motor 3
Start freq 3
13 0 to FU1-20 0.01 49.99 [Hz] Yes
APP-14
Start Frequency of Aux.
Motor 4
Start freq 4
14 0 to FU1-20 0.01 49.99 [Hz] Yes
6-2
APP-15
Stop Frequency of Aux.
Motor 1
Stop freq 1
15 0 to FU1-20 0.01 15.00 [Hz] Yes
APP-16
Stop Frequency of Aux.
Motor 2
Stop freq 2
16 0 to FU1-20 0.01 15.00 [Hz] Yes
APP-17
Stop Frequency of Aux.
Motor 3
Stop freq 3
17 0 to FU1-20 0.01 15.00 [Hz]] Yes
APP-18
Stop Frequency of Aux.
Motor 4
Stop freq 4
18 0 to FU1-20 0.01 15.00 [Hz] Yes
6-2
APP-19
Delay Time before
Operating Aux Motor
Aux start DT
19 0 to 9999 [sec] 0.1 60.0 [sec] Yes
APP-20
Delay Time before
Stopping Aux Motor
Aux stop DT
20 0 to 9999 [sec] 0.1 60.0 [sec] Yes
6-2
APP-21 The Number of Aux Motor
Nbr Aux’s
21 0 to 4 1 4 Yes 6-2
No 0
APP-22 PID Bypass Selection
Regul Bypass
22
Yes 1
- No Yes 6-2
APP-23 Sleep Delay Time
Sleep Delay
23 0 to 9999 [sec] 0.1 60.0 [sec] Yes 6-2
APP-24 Sleep Frequency
Sleep Freq
24 0 to FU1-20 0.01 19.00 [Hz] Yes 6-2
27
Code APP-02 through APP-07 appears only when APP-01 is set to ‘Traverse’.
28