HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
3-1
CHAPTER 3 - QUICK-START PROCEDURES
These Quick-Start Up instructions are for those applications where:
The user wants to get the ACtionMaster inverter started quickly
The factory-preset values are suitable for the user application
The factory-preset values are shown on the ‘Chapter 4 - Parameter List’. The ACtionMaster inverter is configured to
operate a motor at 60Hz (base frequency). If the application requires coordinated control with other controllers, it is
recommended the user become familiar with all parameters and features of the inverter before applying AC power.
1. Mounting the inverter (mount the inverter as described in ‘1.3 Mounting’)
Install in a clean, dry location
Allow a sufficient clearance around top and sides of inverter
The ambient temperature should not exceed 40°C (104°F)
If two or more inverters are installed in an enclosure, add additional cooling
2. Wiring the inverter (connect wiring as described in ‘1.7 Power Terminals’)
AC power should be turned OFF
Verify the AC power matches the nameplate voltage
Remove the screw on the bottom front cover of the inverter for terminal board access (For terminal board access
on 15~ 30HP inverters you must disconnect the keypad cable from the inverter and fully removed the cover)