Chapter 6 - Parameter Description [I/O]
6-45
Setting Range
LCD 7-Seg
Description
Lost Command
11
Lost command detection
Run
12
Inverter running detection
Stop
13
Inverter stop detection
Steady
14
Steady speed detection
INV line
15
COMM line
16
Exchange signal outputs
Ssearch
17
Speed search mode detection
Step pulse
18
Step detection in Auto mode
Seq pulse
19
Sequence detection in Auto mode
Ready
20
Inverter ready detection
Trv. ACC
21
Traverse acceleration frequency
Trv. DEC
22
Traverse deceleration frequency
MMC
23
Used for MMC operation
Zspd Dect 24
0 Rpm detection signal during vector
control
Torq Dect 25
Torque detection signal during vector
and sensorless control.
[FDT-1]
When the output frequency reaches the reference
frequency (target frequency), AXA-AXC terminal is
CLOSED.
[AXA-AXC configured as ‘FDT-1’]
[FDT-2]
AXA-AXC is CLOSED when the reference frequency is in
I/O-43 [FDT Bandwidth] centered on I/O-42 [FDT
Frequency], and the output frequency reaches I/O-43
centered on I/O-42.
[AXA-AXC configured as ‘FDT-2’]
[FDT-3]
AXA-AXC is CLOSED when the output frequency reaches
the band centered on the FDT frequency. The output is
OPENED when the output frequency goes outside the FDT
bandwidth centered on the FDT frequency.
[AXA-AXC configured as ‘FDT-3’]
[FDT-4]
AXA-AXC is CLOSED when the output frequency reaches
the FDT frequency. The output is OPENED when the
output frequency goes below the FDT bandwidth centered
on the FDT frequency.
AXA-AXC
CLOSED
Output Frequency
Time
Time
I/O-43 / 2
I/O-42
Reference Frequency
AXA-
A
XC
CLOSED
Output Frequency
Time
Time
I/O-43 / 2
Reference Frequency
AXA-
A
XC
ON
Output Frequency
Time
Time
I/O-43 / 2
ON
I/O-42