HP (Hewlett-Packard) 30 HP30 Projector User Manual


 
Chapter 5 - Parameter List
5-12
Keypad Display Setting Range
Code Description
LCD 7-Segment LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
I/O-26
Deceleration Time 1
for Step Frequency
Dec time-1
26 0 to 6000 [sec] 0.1 20.0 [sec] Yes
I/O-27 Acceleration Time 2
Acc time-2
27 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-28 Deceleration Time 2
Dec time-2
28 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-29 Acceleration Time 3
Acc time-3
29 0 to 6000 [sec] 0.1 40.0 [sec] Yes
I/O-30 Deceleration Time 3
Dec time-3
30 0 to 6000 [sec] 0.1 40.0 [sec] Yes
I/O-31 Acceleration Time 4
Acc time-4
31 0 to 6000 [sec] 0.1 50.0 [sec] Yes
I/O-32 Deceleration Time 4
Dec time-4
32 0 to 6000 [sec] 0.1 50.0 [sec] Yes
I/O-33 Acceleration Time 5
Acc time-5
33 0 to 6000 [sec] 0.1 40.0 [sec] Yes
I/O-34 Deceleration Time 5
Dec time-5
34 0 to 6000 [sec] 0.1 40.0 [sec] Yes
I/O-35 Acceleration Time 6
Acc time-6
35 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-36 Deceleration Time 6
Dec time-6
36 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-37 Acceleration Time 7
Acc time-7
37 0 to 6000 [sec] 0.1 20.0 [sec] Yes
I/O-38 Deceleration Time 7
Dec time-7
38 0 to 6000 [sec] 0.1 20.0 [sec] Yes
Frequency 0
Current 1
Voltage 2
DC link Vtg 3
I/O-40
FM (Frequency Meter)
Output Selection
FM mode
40
Torque 4
- Frequency Yes
I/O-41 FM Output Adjustment
FM adjust
41 10 to 200 [%] 1 100 [%] Yes
6-2
I/O-42 Frequency Detection Level
FDT freq
42 0 to FU1-20 0.01 30.00 [Hz] Yes
I/O-43
Frequency Detection
Bandwidth
FDT band
43 0 to FU1-20 0.01 10.00 [Hz] Yes
6-2
FDT-1 0
FDT-2 1
FDT-3 2
FDT-4 3
FDT-5 4
OL 5
IOL 6
Stall 7
OV 8
LV 9
OH 10
Lost Command 11
Run 12
Stop 13
Steady 14
INV line 15
COMM line 16
Ssearch 17
I/O-44 Multi-Function Auxiliary
Contact Output Define
(AXA, AXC)
Aux mode
44
Step pulse 18
- Run Yes 6-2