FU1-15: Hold Time
To set the time to maintain holding torque at zero speed
and stop the operation in a shortest time during
Vector_SPD mode operation
The inverter runs to maintain speed 0 for the hold
time in Vector_SPD mode and decelerates to stop
after the hold time elapse.
Operation method during Hold Time:
FU1-7[Stop mode] Decel: speed zero control
FU1-7[Stop mode] DC-brake
FU1-16: Pre-excitation Current
FU1-16 [Pre-excitation Current] is applied during FU1-14.
When the motor magnetic flux increases to match the
rated magnetic flux, pre-excitation current starts to
decrease. When the motor magnetic flux reaches to the
rated magnetic flux, the pre-excitation current matches the
rated pre-excitation current.
Code LCD display Factory setting Setting range
FU1-16 Flux Force 100 [%] 100 ~ 500 [%]
FU1-20: Maximum Frequency
FU1-21: Base Frequency
FU1-22: Starting Frequency
FU1-20 [Maximum Frequency] is the maximum output
frequency of the inverter. Make sure this maximum
frequency does not exceed the rated speed of the motor.
FU1-21 [Base Frequency] is the frequency where the
inverter outputs its rated voltage. In case of using a 50Hz
motor, set this to 50Hz.
FU1-22 [Starting Frequency] is the frequency where the
inverter starts to output its voltage.
Output
Voltage
[V]
Output Speed
[Hz or Rpm]
Hold time
FX-CM
Motor magnetic flux
Excited current
FU1
M
ax freq
20 60.00 Hz
60.00 20
Factory Default: 60.00 Hz 60.00
FU1
Base freq
21 60.00 Hz
60.00 21
Factory Default: 60.00 Hz 60.00
FU1
Start freq
22 0.50 Hz
0.50 22
Factory Default: 0.50 Hz 0.50
FU1
Hold Time
15 1000 ms
1000 15
Factory Default: 1000 ms 1000
FU1
Flux Force
16 100.0 %
1 00.0 16
Factory Default: 100.0 % 100.0
Related Functions: FU2-34 [No Load Motor Current (RMS)]
FU1-14 [Pre-excitation Time]