Omron C200HG Computer Hardware User Manual


 
177
5-15-7 ONE DIGIT SHIFT LEFT SLD(74)
Ladder Symbols Operand Data Areas
SLD(74)
St
E
@SLD(74)
St
E
St: Starting word
IR, SR, AR, DM, HR, LR
E: End word
IR, SR, AR, DM, HR, LR
Limitations St and E must be in the same data area, and St must be less than or equal to E.
Description When the execution condition is OFF, SLD(74) is not executed. When the execu-
tion condition is ON, SLD(74) shifts data between St and E (inclusive) by one
digit (four bits) to the left. 0 is written into the rightmost digit of the St, and the
content of the leftmost digit of E is lost.
5
E
8 1
St
F C 97D
Lost data 0
...
Precautions If a power failure occurs during a shift operation across more than 50 words, the
shift operation might not be completed.
Flags ER: The St and E words are in different areas, or St is greater than E.
Indirectly addressed DM word is non-existent. (Content of DM word is
not BCD, or the DM area boundary has been exceeded.)
5-15-8 ONE DIGIT SHIFT RIGHT SRD(75)
Ladder Symbols Operand Data Areas
SRD(75)
E
St
@SRD(75)
E
St
E: End word
IR, SR, AR, DM, HR, LR
St: Starting word
IR, SR, AR, DM, HR, LR
Limitations St and E must be in the same data area, and St must be less than or equal to E.
Description When the execution condition is OFF, SRD(75) is not executed. When the
execution condition is ON, SRD(75) shifts data between St and E (inclusive) by
one digit (four bits) to the right. 0 is written into the leftmost digit of St and the
rightmost digit of E is lost.
2
St
3 1
E
4 5 C8F
Lost data
0
...
Data Shifting Section 5-15