Omron C200HG Computer Hardware User Manual


 
454
10-1 Host Link Command Summary
Command Chart The commands listed in the chart below can be used for host link communica-
tions with the C200HX/HG/HE.
Header code
PC mode
Name Page
RUN MON PRG
RR Valid Valid Valid IR/SR AREA READ 458
RL Valid Valid Valid LR AREA READ 459
RH Valid Valid Valid HR AREA READ 460
RC Valid Valid Valid PV READ 461
RG Valid Valid Valid TC STATUS READ 462
RD Valid Valid Valid DM AREA READ 463
RJ Valid Valid Valid AR AREA READ 464
RE Valid Valid Valid EM AREA READ 464
WR Not valid Valid Valid IR/SR AREA WRITE 465
WL Not valid Valid Valid LR AREA WRITE 466
WH Not valid Valid Valid HR AREA WRITE 467
WC Not valid Valid Valid PV WRITE 468
WG Not valid Valid Valid TC STATUS WRITE 469
WD Not valid Valid Valid DM AREA WRITE 470
WJ Not valid Valid Valid AR AREA WRITE 471
WE Not valid Valid Valid EM AREA WRITE 472
R# Valid Valid Valid SV READ 1 473
R$ Valid Valid Valid SV READ 2 474
R% Valid Valid Valid SV READ 3 476
W# Not valid Valid Valid SV CHANGE 1 477
W$ Not valid Valid Valid SV CHANGE 2 478
W% Not valid Valid Valid SV CHANGE 3 480
MS Valid Valid Valid STATUS READ 481
SC Valid Valid Valid STATUS WRITE 483
MF Valid Valid Valid ERROR READ 484
KS Not valid Valid Valid FORCED SET 485
KR Not valid Valid Valid FORCED RESET 486
FK Not valid Valid Valid MULTIPLE FORCED SET/RESET 488
KC Not valid Valid Valid FORCED SET/RESET CANCEL 489
MM Valid Valid Valid PC MODEL READ 490
TS Valid Valid Valid TEST 491
RP Valid Valid Valid PROGRAM READ 492
WP Not valid Not valid Valid PROGRAM WRITE 493
MI Not valid Not valid Valid I/O TABLE GENERATE 494
QQ Valid Valid Valid COMPOUND COMMAND 495
XZ Valid Valid Valid ABORT (command only) 497
 Valid Valid Valid INITIALIZE (command only) 498
EX Valid Valid Not valid TXD RESPONSE (response only) 498
IC --- --- --- Undefined command (response only) 499
Host Link Command Summary Section 10-1