Sun Microsystems SL8500 Computer Drive User Manual


 
Library Specifications
96154 Revision K Chapter 1 Introduction 25
Library Specifications
TABLE 1-8 Library Specifications
Physical
•Hmeight
•Width
Depth (Base Library)
With 1 expansion module
With 2 expansion modules
With 3 expansion modules
2.37 m (236.6 cm) or 7.76 ft (93.15 in.)
1.7 m (170.8 cm) or 5.6 ft (67.25 in.)
2.8 m (276.9 cm) or 9.1 ft (109 in.)
3.7 m (372.1 cm) or 12.2 ft (146.5 in.)
4.7 m (467.4 cm) or 15.3 ft (184 in.)
5.6 m (562.6 cm) or 18.5 ft (221.5 in.)
•Weights
Base Library
With 1 expansion module
With 2 expansion modules
With 3 expansion modules
Weight distribution per pad
Library only:
1954 kg (4,309 lb)
2392 kg (5,274 lb)
2830 kg (6,239 lb)
3396 kg (7,487 lb)
454 kg (1,000 lb)
•Pass-thru Port
Height
Width
Depth
Weight
231 cm (91 in.)
17.2 cm (6.76 in.)
150.8 cm (59.4 in.)
121 kg (266 lb) including the mechanisms
Service Clearances
Customer Interface Module
Drive & Electronics Module
Pass-thru port (between)
66 cm (26 in.)
85 cm (33.5 in.)
15.24 cm (6 in.)
Temperature
Operating
Shipping
Storing
+16 to +32°C (+60 to +90°F)
-30.5 to +49°C (-23 to +120°F)
+4.4 to +32°C (+40 to +90°F)
+25.6°C (+78°F) maximum, non-condensing
Wet bulb (operating)
Humidity
Operating
Shipping
Storing
20% to 80%
5% to 90%
20% to 80%
Operating Heat Output 44,380 Btu/hr (maximum loading**)
Calculation for this is: 3.41214 x Watts = Btu/hr
Power Consumption
Single phase configuration and three phase
configurations
13.0 kW (maximum loading**)
13.7 kVA
kVA = kWatts ÷ Power factor
The power factor for the SL8500 = 0.95
**Maximum loading includes 64 tape drives, 4 fully loaded racks, 8 HandBots, all the front frame components
(CAPs, service door, and elevators), plus redundant control modules.