Fujitsu M9000 Server User Manual


 
19-6 SPARC Enterprise M8000/M9000 Servers Service Manual June 2010
7. Mount the replacement DDC by following the removal instructions in Step 5
and Step 6 in reverse order. Align the DDC with the slot guides, insert it
carefully, and secure it firmly.
Push the bottom eject/lock lever as far as it will go, and then push the knob screw
on the lever to lock it in position. If the knob screws remain in position, the DDC
is securely mounted.
Caution – Do not forcibly push the DDC when inserting it, even if it is not moving
smoothly. If the DDC is forcibly inserted despite the presence of any obstruction in a
slot or any problem with a connector pin, serious damage may result.
8. Go back to the terminal that is connected to the XSCF, and enter data according
to the guidance of the maintenance menu displayed after replacement.
a. Perform this operation according to instructions in messages. The operation
is completed when the display of the maintenance menu returns to the
initial page.
b. Exit the maintenance menu.
9. Using the XSCF command showhardconf or showstatus, confirm that each
replacement component is normal.
Unless "*" is displayed for the replacement DDC, it is operating normally.
For details of the showhardconf command and showstatus command, see the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide,
the SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference
Manual, or the man page.
Note – The showstatus command displays information on degraded components.
10. Close and lock the door of the server.