GE EPM 9650/9800 Computer Monitor User Manual


 
Address Line Pt
DNP
Ob
j
Description Range Units Type R/W
03741-03744 291 5 20 obsolete-TOU Prior Month Reg 2 Watthour (Quadrant 2 + 3) 0 Wh / -9,999,999,999,999,999 Wh
1 W
H
F20 R
03745-03748 291 6 20 obsolete-TOU Prior Month Reg 2 VAhour (Quadrant 2) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
03749-03752 291 7 20 obsolete-TOU Prior Month Reg 2 VARhour (Quadrant 2) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
03753-03756 291 8 20 obsolete-TOU Prior Month Reg 2 VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
03757-03760 291 9 20 obsolete-TOU Prior Month Reg 2 VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
03761-03762 292 0 30 TOU Prior Month Reg 2 Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
03763-03764 292 1 30 TOU Prior Month Reg 2 Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
03765-03766 292 2 30 TOU Prior Month Reg 2 Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
03767-03768 292 3 30 TOU Prior Month Reg 2 Peak Demand VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
03769-03770 293 0 30 TOU Prior Month Reg 2 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
03771-03772 293 1 30 TOU Prior Month Reg 2 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
03773-03776 294 0 50 TOU Prior Month Reg 2 Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
03777-03780 294 1 50 TOU Prior Month Reg 2 Peak Demand Watt (Q 2 + 3) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
03781-03784 294 2 50 TOU Prior Month Reg 2 Peak Demand VAR (Q 1 + 2) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
03785-03788 294 3 50 TOU Prior Month Reg 2 Peak Demand VAR (Q 3 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
03789-03792 295 0 20 obsolete-TOU Prior Month Reg 3 Watthour (Quadrant 1 + 4) +9,999,999,999,999,999 Wh / 0 Wh
1 W
H
F20 R
03793-03796 295 1 20 obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 1) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
03797-03800 295 2 20 obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 1) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
03801-03804 295 3 20 obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 4) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
03805-03808 295 4 20 obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 4) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
03809-03812 295 5 20 obsolete-TOU Prior Month Reg 3 Watthour (Quadrant 2 + 3) 0 Wh / -9,999,999,999,999,999 Wh
1 W
H
F20 R
03813-03816 295 6 20 obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 2) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
03817-03720 295 7 20 obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 2) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
03821-03824 295 8 20 obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
03825-03828 295 9 20 obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
03829-03830 296 0 30 TOU Prior Month Reg 3 Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
03831-03832 296 1 30 TOU Prior Month Reg 3 Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
03833-03834 296 2 30 TOU Prior Month Reg 3 Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
03835-03836 296 3 30 TOU Prior Month Reg 3 Peak Demand VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
03837-03838 297 0 30 TOU Prior Month Reg 3 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
03839-03840 297 1 30 TOU Prior Month Reg 3 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
03841-03844 298 0 50 TOU Prior Month Reg 3 Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
Time of Use Prior Month Reg 3 Block