Address Line Pt
DNP
Ob
j
Description Range Units Type R/W
53259 Phase B Watt + 1500 W / - 1500 W 1500 / 2048 W sec F59 R
53260 Phase C Watt + 1500 W / - 1500 W 1500 / 2048 W sec F59 R
53261 Phase A VAR + 1500 VAR / - 1500 VAR 1500 / 2048 F59 R
53262 Phase B VAR + 1500 VAR / - 1500 VAR 1500 / 2048 F59 R
53263 Phase C VAR + 1500 VAR / - 1500 VAR 1500 / 2048 F59 R
53264-53265 Reserved
53266 Computed Neutral Current + 5 A / 0 A 5 / 2048 A sec F59 R
53267-53268 Positive Watthour + 99,999,999 kWh / 0 kWh 1 kWh pri F60 R
53269-53270 Negative Watthour 0 kWh / - 99,999,999 kWh 1 kWh pri F60 R
53271-53272 Positive VARhour + 99,999,999 kVARh / 0 kVARh 1 kVARh pri F60 R
53273-53274 Negative VARhour 0 kVARh / - 99,999,999 kVARh 1 kVARh pri F60 R
53275 Frequency 45 Hz / 75 Hz 30 / 4096 Hz F61 R
53276-53347 Reserved
53348 Energy Reset W
57345 Log Reset W
57346 Maximum Reset W
57347 Minimum Reset W
57348 Energy Reset W
57349 Calibrate 120 V R/W
57350 Calibrate 150 mA R/W
57351 Calibrate 250 mA R/W
57352 Calibrate 500 mA R/W
57353 Calibrate 1 A R/W
57354 Calibrate 2.5 A R/W
57355 Calibrate 5 A R/W
57356 Calibrate Automatic R/W
57357 Calibrate +1 A Phase R/W
57358 Calibrate -1 A Phase R/W
57359 Calibrate +1 B Phase R/W
57360 Calibrate -1 B Phase R/W
57361 Calibrate +1 C Phase R/W
57362 Calibrate -1 C Phase R/W
Action Block