![](http://pdfasset.owneriq.net/9/ea/9eacc88e-090c-4215-bb30-08da2572cdf1/9eacc88e-090c-4215-bb30-08da2572cdf1-bg149.png)
7-9
7.15: Device Label Settings Block (45969-45992).
• Meter Designation - 8 registers, 16 bytes ASCII.
• Auxiliary Voltage Label - 8 registers, 16 bytes ASCII.
• Measured Neutral Current Label - 8 registers, 16 bytes ASCII.
7.16: Network Settings Block (45993-46016).
• IP Address - 2 registers, 4 bytes. Each byte has unsigned integer value.
• Subnet Mask - 2 registers, 4 bytes. Each byte has unsigned integer value.
• Default Gateway - 2 registers, 4 bytes. Each byte has unsigned integer value.
• Port 2 Baud Rate - 1 byte, unsigned integer.
• Gateway Delay - 1 byte, unsigned integers.
Mode 1 - Network Mode 1. 1 register, only High Byte is used.
Bit 7: IP Address Resolution
A bit value of 1 means use DHCP server.
A bit value of 0 means use static IP address programmed into the meter.
Bits 0-6: Reserved
• Computer Name - 8 registers, 16 bytes ASCII.
• Server IP Address - 2 registers, 4 bytes. Each byte has unsigned integer values.
Value Baud Rate
0 4800
1 9600
2 19200
3 38400
4 57600
5 115200
Port 2 Baud Rate Values
Delays in milliseconds (ms)Value
00
115
2-255 30-3825
Gateway Delay in Milliseconds