7-21
7.33: Custom DNP Definition Block for Analog Input (Object 30) (47105-47360)
• Line number: 2-byte unsigned integer
Line number and Point number will indicate the Analog Input value to be used for one of the
point in Object 30.
• Point number: 1-byte unsigned integer
• Reserved: 1 byte. Reserved for future use.
• DeadBand: 2-byte signed number (Percentage)
Range: +327.67% / - 327.68%
Unit: 0.01%
If the Current Analog Value is different from the Previous value by more than Deadband
percentage, the meter will generate Analog Change Event value if it is assigned to any Class.
• Class assignments (Currently only bits 5,4 and 3 are used): 8-bit bitmap
When bit 5 is set, the Analog Change Event value will not be generated.
When bit 5 is clear, bit 4 and bit 3 will assign the Analog Change Event value to a Class.
• Reserved: 1 byte. Reserved for future use.
7.34: Custom DNP Definition Block for Binary Counter (Object 20) (47361-47424)
• Line number: 2-byte unsigned integer
Line number and Point number will indicate the Binary Counter value to be used for one of the
point in Object 20.
• Point number: 1-byte unsigned integer
• Scaling: 1-byte unsigned integer
Range: 0-15
Class Assignments for Analog Change Event
Bit 5 Bit 4 Bit 3 Class Assigned
0 0 0 No Class
0 0 1 Class 1
0 1 0 Class 2
0 1 1 Class 3
1 X X No Class
1 X X No Class
1 X X No Class
1 X X No Class