GE EPM 9650/9800 Computer Monitor User Manual


 
Address Line Pt
DNP
Ob
j
Description Range Units Type R/W
06460 485 2 30 Quadrant 2 Watthour in the Interval, Secondary 65,535 / 0
1 W
H
F57 R
06461 485 3 30 Quadrant 3 Watthour in the Interval, Secondary 65,535 / 0
1 W
H
F57 R
06462 486 0 30 Quadrant 1 Vahour in the Interval, Secondary 65,535 / 0
1 VA
H
F57 R
06463 486 1 30 Quadrant 1 VARhour in the Interval, Secondary 65,535 / 0
1 VAR
H
F57 R
06464 486 2 30 Quadrant 4 Vahour in the Interval, Secondary 65,535 / 0
1 VA
H
F57 R
06465 486 3 30 Quadrant 4 VARhour in the Interval, Secondary 65,535 / 0
1 VAR
H
F57 R
06466 486 4 30 Quadrant 2 Vahour in the Interval, Secondary 65,535 / 0
1 VA
H
F57 R
06467 486 5 30 Quadrant 2 VARhour in the Interval, Secondary 65,535 / 0
1 VAR
H
F57 R
06468 486 6 30 Quadrant 3 Vahour in the Interval, Secondary 65,535 / 0
1 VA
H
F57 R
06469 486 7 30 Quadrant 3 VARhour in the Interval, Secondary 65,535 / 0
1 VAR
H
F57 R
06470-06471 487 0 30 Quadrant 1 Watthour in the Interval, Primary 4,294,967,295 / 0
1 W
H
F18 R
06472-06473 487 1 30 Quadrant 4 Watthour in the Interval, Primary 4,294,967,295 / 0
1 W
H
F18 R
06474-06475 487 2 30 Quadrant 2 Watthour in the Interval, Primary 4,294,967,295 / 0
1 W
H
F18 R
06476-06477 487 3 30 Quadrant 3 Watthour in the Interval, Primary 4,294,967,295 / 0
1 W
H
F18 R
06478-06479 488 0 30 Total Vahour (Quadrants 1+2+3+4) in the Interval, Primary 4,294,967,295 / 0
1 VA
H
F18 R
06480-06481 488 1 30 Positive VARhour (Quadrants 1+2) in the Interval, Primary 4,294,967,295 / 0
1 VAR
H
F18 R
06482-06483 488 2 30 Negative VARhour (Quadrants 3+4) in the Interval, Primary 4,294,967,295 / 0
1 VAR
H
F18 R
06484 489 0 30 KYZ Pulse Output in the Interval, Relay 1 65,535 / 0 1 pulse F57 R
06485 489 1 30 KYZ Pulse Output in the Interval, Relay 2 65,535 / 0 1 pulse F57 R
06486 489 2 30 KYZ Pulse Output in the Interval, Relay 3 65,535 / 0 1 pulse F57 R
06487 489 3 30 KYZ Pulse Output in the Interval, Relay 4 65,535 / 0 1 pulse F57 R
06488 489 4 30 KYZ Pulse Output in the Interval, IR LED 65,535 / 0 1 pulse F57 R
06489 490 0 30 Short Term Flicker Countdown 65,535 / 0 1 second F56 R
06490 490 1 30 Long Term Flicker Countdown 65,535 / 0 1 second F56 R
06491-06494 491 0 50 Cumulative Demand Block Time Stamp 12/31/9999 23:59:59.99 F3 R
06495-06496 492 0 30 Positive Watt (Quadrants 1+4) Cumulative Demand 4,294,967,295 / 0 F18 R
06497-06498 492 1 30 Negative Watt (Quadrants 2+3) Cumulative Demand 4,294,967,295 / 0 F18 R
06499-06500 493 0 30 Positive Watt (Quadrants 1+4) Continuous Cumulative Demand 4,294,967,295 / 0 F18 R
06501-06502 493 1 30 Negative Watt (Quadrants 2+3) Continuous Cumulative Demand 4,294,967,295 / 0 F18 R
06503-06504 494 0 30 TOU Active Reg1 Cumulative Demand Q1 + Q4 Watt 4,294,967,295 / 0 F18 R
Flicker Countdown Block
Cumulative Demand Block
Time of Use Active Cumulative Demand
2- 98