DNP
Ob
j
Description Range Units Type R/W
04171-04172 316 1 30 TOU Prior Month Reg 8 Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
04173-04174 316 2 30 TOU Prior Month Reg 8 Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
04175-04176 316 3 30 TOU Prior Month Reg 8 Peak Demand VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04177-04178 317 0 30 TOU Prior Month Reg 8 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
04179-04180 317 1 30 TOU Prior Month Reg 8 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04181-04184 318 0 50 TOU Prior Month Reg 8 Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04185-04188 318 1 50 TOU Prior Month Reg 8 Peak Demand Watt (Q 2 + 3) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04189-04192 318 2 50 TOU Prior Month Reg 8 Peak Demand VAR (Q 1 + 2) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04193-04196 318 3 50 TOU Prior Month Reg 8 Peak Demand VAR (Q 3 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04197-04200 319 0 20 obsolete-TOU Prior Month Total Watthour (Quadrant 1 + 4) +9,999,999,999,999,999 Wh / 0 Wh
1 W
H
F20 R
04201-04204 319 1 20 obsolete-TOU Prior Month Total VAhour (Quadrant 1) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04205-04208 319 2 20 obsolete-TOU Prior Month Total VARhour (Quadrant 1) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04209-04212 319 3 20 obsolete-TOU Prior Month Total VAhour (Quadrant 4) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04213-04216 319 4 20 obsolete-TOU Prior Month Total VARhour (Quadrant 4) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04217-04220 319 5 20 obsolete-TOU Prior Month Total Watthour (Quadrant 2 + 3) 0 Wh / -9,999,999,999,999,999 Wh
1 W
H
F20 R
04221-04224 319 6 20 obsolete-TOU Prior Month Total VAhour (Quadrant 2) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04225-04228 319 7 20 obsolete-TOU Prior Month Total VARhour (Quadrant 2) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04229-04232 319 8 20 obsolete-TOU Prior Month Total VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04233-04236 319 9 20 obsolete-TOU Prior Month Total VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04237-04238 320 0 30 TOU Prior Month Total Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
04239-04240 320 1 30 TOU Prior Month Total Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
04241-04242 320 2 30 TOU Prior Month Total Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
04243-04244 320 3 30 TOU Prior Month Total Peak Demand Del. VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04245-04246 321 0 30 TOU Prior Month Total Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
04247-04248 321 1 30 TOU Prior Month Total Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04249-04252 322 0 50 TOU Prior Month Total Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04253-04256 322 1 50 TOU Prior Month Total Peak Demand Watt (Q 2 + 3) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04257-04260 322 2 50 TOU Prior Month Total Peak Demand VAR (Q 1 + 2) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04261-04264 322 3 50 TOU Prior Month Total Peak Demand VAR (Q 3 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04265-04268 323 0 20 obsolete-TOU Active Reg 1 Watthour (Quadrant 1 + 4) +9,999,999,999,999,999 Wh / 0 Wh
1 W
H
F20 R
04269-04272 323 1 20 obsolete-TOU Active Reg 1 VAhour (Quadrant 1) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
Time of Use Prior Month Total Block
Time of Use Active Reg 1 Block
2- 76