GE EPM 9650/9800 Computer Monitor User Manual


 
Address Line Pt
DNP
Ob
j
Description Range Units Type R/W
00469 116 2 30 Minimum Thermal Average Phase C Power Factor Quadrant 1 0.999 / 0 0.001 PF F8 R
00470 117 0 30 Minimum Thermal Average Power Factor Quadrant 1 0.999 / 0 0.001 PF F8 R
00471 118 0 30 Minimum Thermal Average Phase A Power Factor Quadrant 2 1.999 / /1.000 0.001 PF F8 R
00472 118 1 30 Minimum Thermal Average Phase B Power Factor Quadrant 2 1.999 / /1.000 0.001 PF F8 R
00473 118 2 30 Minimum Thermal Average Phase C Power Factor Quadrant 2 1.999 / /1.000 0.001 PF F8 R
00474 119 0 30 Minimum Thermal Average Power Factor Quadrant 2 1.999 / /1.000 0.001 PF F8 R
00475 120 0 30 Minimum Thermal Average Phase A Power Factor Quadrant 3 2.999 / 2.000 0.001 PF F8 R
00476 120 1 30 Minimum Thermal Average Phase B Power Factor Quadrant 3 2.999 / 2.000 0.001 PF F8 R
00477 120 2 30 Minimum Thermal Average Phase C Power Factor Quadrant 3 2.999 / 2.000 0.001 PF F8 R
00478 121 0 30 Minimum Thermal Average Power Factor Quadrant 3 2.999 / 2.000 0.001 PF F8 R
00479 122 0 30 Minimum Thermal Average Phase A Power Factor Quadrant 4 3.999 / 3.000 0.001 PF F8 R
00480 122 1 30 Minimum Thermal Average Phase B Power Factor Quadrant 4 3.999 / 3.000 0.001 PF F8 R
00481 122 2 30 Minimum Thermal Average Phase C Power Factor Quadrant 4 3.999 / 3.000 0.001 PF F8 R
00482 123 0 30 Minimum Thermal Average Power Factor Quadrant 4 3.999 / 3.000 0.001 PF F8 R
00483 124 0 30 Minimum Thermal Average Voltage Imbalance +327.67% / -327.68% 0.01% F10 R
00484 124 1 30 Minimum Thermal Average Current Imbalance +327.67% / -327.68% 0.01% F10 R
00485 125 0 30 Minimum THD Phase A-N Voltage / Phase A-B Voltage +327.67% / -327.68% 0.01% F10 R
00486 125 1 30 Minimum THD Phase B-N Voltage / Phase B-C Voltage +327.67% / -327.68% 0.01% F10 R
00487 125 2 30 Minimum THD Phase C-N Voltage / Phase C-A Voltage +327.67% / -327.68% 0.01% F10 R
00488 126 0 30 Minimum THD Phase A Current +327.67% / -327.68% 0.01% F10 R
00489 126 1 30 Minimum THD Phase B Current +327.67% / -327.68% 0.01% F10 R
00490 126 2 30 Minimum THD Phase C Current +327.67% / -327.68% 0.01% F10 R
00491 127 0 30 Minimum K-Factor Phase A Current +327.67% / -327.68% 0.01% F10 R
00492 127 1 30 Minimum K-Factor Phase B Current +327.67% / -327.68% 0.01% F10 R
00493 127 2 30 Minimum K-Factor Phase C Current +327.67% / -327.68% 0.01% F10 R
00494-00495 128 0 30 Coincident Thermal Average VAR for Minimum Positive Watt +32767 VAR / -32768 VAR 1/ 65536 W sec F7 R
00496-00497 128 1 30 Coincident Thermal Average VAR for Minimum Negative Watt +32767 VAR / -32768 VAR 1/ 65536 W sec F7 R
00498-00501 129 0 50 Maximum Thermal Average Phase A-N Voltage Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
00502-00505 129 1 50 Maximum Thermal Average Phase B-N Voltage Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
00506-00509 129 2 50 Maximum Thermal Average Phase C-N Voltage Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
00510-00513 129 3 50 Maximum Thermal Average Auxiliary Voltage Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
00514-00517 129 4 50 Maximum Thermal Average Phase A Current Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
Maximum Time Stamp Block