The EPM Modbus Register Map can be found in Chapter 2. This chapter gives a detailed
description of each of the Programmable Settings Blocks.
7.1: Communication Settings Block (45057-45074)
Device Address - 2 bytes, unsigned integer, ranging from 0000H to FFFFH
Protocol - 1 byte, unsigned integer.
Baud Rate - 1 byte, unsigned integer.
Parity - 1 byte, unsigned integer.
Stop Bits - 1 byte, unsigned integer.
Data Bits - 1 byte, unsigned integer.
Response Delay - 1 byte, unsigned integer.
Port Mode - 1 byte, unsigned integer. The value 1 means Master; value 0 means Slave. Port 1 is
always a Slave.
7.2: Limit Settings Block (45077-45204)
Limit Comparisons - Internal Representations
An EPM device has 32 Limits Objects.
Q
Each Limit Object performs two independent comparisons with a selected computed value and
combines them into a combined output. Information needed to perform these actions: channel
identification, comparison values, comparison directions and combination type.
Communication Settings Block Specifications
0 Modbus ASCII 4800 None 5 0.00
1 Modbus RTU 9600 Even 6 0.25
2 DNP 3.0 19200 Odd 7 0.50
3 38400 Mark 8 0.75
4 57600 Space 1.00
5 115200 1.25
6 1.50
7 1 stop 1.75
8 1.5 stop 2.00
9-14 2.25-3.50
15 2 stop 3.75
16-255 4.00-63.75
Value Protocol Parity Stop Bits Data Bits Response Delay (ms)Baud Rate