GE EPM 9650/9800 Computer Monitor User Manual


 
Address Line Pt
DNP
Ob
j
Description Range Units Type R/W
04061-04064 311 0 20 obsolete-TOU Prior Month Reg 7 Watthour (Quadrant 1 + 4) +9,999,999,999,999,999 Wh / 0 Wh
1 W
H
F20 R
04065-04068 311 1 20 obsolete-TOU Prior Month Reg 7 VAhour (Quadrant 1) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04069-04072 311 2 20 obsolete-TOU Prior Month Reg 7 VARhour (Quadrant 1) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04073-04076 311 3 20 obsolete-TOU Prior Month Reg 7 VAhour (Quadrant 4) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04077-04080 311 4 20 obsolete-TOU Prior Month Reg 7 VARhour (Quadrant 4) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04081-04084 311 5 20 obsolete-TOU Prior Month Reg 7 Watthour (Quadrant 2 + 3) 0 Wh / -9,999,999,999,999,999 Wh
1 W
H
F20 R
04085-04088 311 6 20 obsolete-TOU Prior Month Reg 7 VAhour (Quadrant 2) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04089-04092 311 7 20 obsolete-TOU Prior Month Reg 7 VARhour (Quadrant 2) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04093-04096 311 8 20 obsolete-TOU Prior Month Reg 7 VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04097-04100 311 9 20 obsolete-TOU Prior Month Reg 7 VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04101-04102 312 0 30 TOU Prior Month Reg 7 Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
04103-04104 312 1 30 TOU Prior Month Reg 7 Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
04105-04106 312 2 30 TOU Prior Month Reg 7 Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
04107-04108 312 3 30 TOU Prior Month Reg 7 Peak Demand VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04109-04110 313 0 30 TOU Prior Month Reg 7 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
04111-04112 313 1 30 TOU Prior Month Reg 7 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04113-04116 314 0 50 TOU Prior Month Reg 7 Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04117-04120 314 1 50 TOU Prior Month Reg 7 Peak Demand Watt (Q 2 + 3) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04121-04124 314 2 50 TOU Prior Month Reg 7 Peak Demand VAR (Q 1 + 2) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04125-04128 314 3 50 TOU Prior Month Reg 7 Peak Demand VAR (Q 3 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04129-04132 315 0 20 obsolete-TOU Prior Month Reg 8 Watthour (Quadrant 1 + 4) +9,999,999,999,999,999 Wh / 0 Wh
1 W
H
F20 R
04133-04136 315 1 20 obsolete-TOU Prior Month Reg 8 VAhour (Quadrant 1) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04137-04140 315 2 20 obsolete-TOU Prior Month Reg 8 VARhour (Quadrant 1) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04141-04144 315 3 20 obsolete-TOU Prior Month Reg 8 VAhour (Quadrant 4) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04145-04148 315 4 20 obsolete-TOU Prior Month Reg 8 VARhour (Quadrant 4) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04149-04152 315 5 20 obsolete-TOU Prior Month Reg 8 Watthour (Quadrant 2 + 3) 0 Wh / -9,999,999,999,999,999 Wh
1 W
H
F20 R
04153-04156 315 6 20 obsolete-TOU Prior Month Reg 8 VAhour (Quadrant 2) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04157-04160 315 7 20 obsolete-TOU Prior Month Reg 8 VARhour (Quadrant 2) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04161-04164 315 8 20 obsolete-TOU Prior Month Reg 8 VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04165-04168 315 9 20 obsolete-TOU Prior Month Reg 8 VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04169-04170 316 0 30 TOU Prior Month Reg 8 Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
Time of Use Prior Month Reg 7 Block
Time of Use Prior Month Reg 8 Block
2- 75