GE EPM 9650/9800 Computer Monitor User Manual


 
Address Line Pt
DNP
Ob
j
Description Range Units Type R/W
04705-04708 347 8 20 obsolete-TOU Active Reg 7 VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04709-04712 347 9 20 obsolete-TOU Active Reg 7 VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04713-04714 348 0 30 TOU Active Reg 7 Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
04715-04716 348 1 30 TOU Active Reg 7 Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
04717-04718 348 2 30 TOU Active Reg 7 Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
04719-04720 348 3 30 TOU Active Reg 7 Peak Demand VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04721-04722 349 0 30 TOU Active Reg 7 Coin. Dmd. VAR to Peak Dmd. Watt (Quadrant 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
04723-04724 349 1 30 TOU Active Reg 7 Coin. Dmd. VAR to Peak Dmd. Watt (Quadrant 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04725-04728 350 0 50 TOU Active Reg 7 Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04729-04732 350 1 50 TOU Active Reg 7 Peak Demand Watt (Q 2 + 3) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04733-04736 350 2 50 TOU Active Reg 7 Peak Demand VAR (Q 1 + 2) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04737-04740 350 3 50 TOU Active Reg 7 Peak Demand VAR (Q 3 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04741-04744 351 0 20 obsolete-TOU Active Reg 8 Watthour (Quadrant 1 + 4) +9,999,999,999,999,999 Wh / 0 Wh
1 W
H
F20 R
04745-04748 351 1 20 obsolete-TOU Active Reg 8 VAhour (Quadrant 1) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04749-04752 351 2 20 obsolete-TOU Active Reg 8 VARhour (Quadrant 1) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04753-04756 351 3 20 obsolete-TOU Active Reg 8 VAhour (Quadrant 4) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04757-04760 351 4 20 obsolete-TOU Active Reg 8 VARhour (Quadrant 4) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04761-04764 351 5 20 obsolete-TOU Active Reg 8 Watthour (Quadrant 2 + 3) 0 Wh / -9,999,999,999,999,999 Wh
1 W
H
F20 R
04765-04768 351 6 20 obsolete-TOU Active Reg 8 VAhour (Quadrant 2) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04769-04772 351 7 20 obsolete-TOU Active Reg 8 VARhour (Quadrant 2) +9,999,999,999,999,999 VARh / 0 VARh
1 VAR
H
F20 R
04773-04776 351 8 20 obsolete-TOU Active Reg 8 VAhour (Quadrant 3) +9,999,999,999,999,999 VAh / 0 VAh
1 VA
H
F20 R
04777-04780 351 9 20 obsolete-TOU Active Reg 8 VARhour (Quadrant 3) 0 VARh / -9,999,999,999,999,999 VARh
1 VAR
H
F20 R
04781-04782 352 0 30 TOU Active Reg 8 Peak Demand Watt (Quadrant 1 + 4) +32767 Watt / 0 Watt 1/ 65536 W sec F7 R
04783-04784 352 1 30 TOU Active Reg 8 Peak Demand Watt (Quadrant 2 + 3) 0 Watt / -32768 Watt 1/ 65536 W sec F7 R
04785-04786 352 2 30 TOU Active Reg 8 Peak Demand VAR (Quadrant 1 + 2) +32767 VAR / 0 VAR 1/ 65536 VAR sec F7 R
04787-04788 352 3 30 TOU Active Reg 8 Peak Demand VAR (Quadrant 3 + 4) 0 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04789-04790 353 0 30 TOU Active Reg 8 Coin. Dmd. VAR to Peak Dmd. Watt (Quadrant 1 + 4) +32767 VAR/ -32768 VAR 1/ 65536 VAR sec F7 R
04791-04792 353 1 30 TOU Active Reg 8 Coin. Dmd. VAR to Peak Dmd. Watt (Quadrant 2 + 3) +32767 VAR / -32768 VAR 1/ 65536 VAR sec F7 R
04793-04796 354 0 50 TOU Active Reg 8 Peak Demand Watt (Q 1 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04797-04800 354 1 50 TOU Active Reg 8 Peak Demand Watt (Q 2 + 3) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04801-04804 354 2 50 TOU Active Reg 8 Peak Demand VAR (Q 1 + 2) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
04805-04808 354 3 50 TOU Active Reg 8 Peak Demand VAR (Q 3 + 4) Time Stamp 12/31/9999 23:59:59.99 10 msec F3 R
Time of Use Active Reg 8 Block