![](http://pdfasset.owneriq.net/9/ea/9eacc88e-090c-4215-bb30-08da2572cdf1/9eacc88e-090c-4215-bb30-08da2572cdf1-bg14a.png)
7-10
Mode 2 - Network Mode 2. 1 byte.
Bit 7: IP Address Resolution
A bit value of 1 means use DHCP server.
A bit value of 0 means use static IP address programmed into the meter.
Bits 0-6: Reserved
• DNS Server 1 IP Address - 2 registers, 4 bytes. Each byte has unsigned integer values.
• DNS Server 2 IP Address - 2 registers, 4 bytes. Each byte has unsigned integer values.
• Server / Service Enable Bits - 32 Bits.
Bit 31: Undefined
Bit 30: Modbus TCP Client
Bit 29: GE EGD Data Port Server
Bit 28: Web Server
Bit 27: SMPT Client (Email)
Bit 26: FTP Server
Bit 25: FTP Client
Bit 24: HTTP / Modbus RTU Server
Bit 0 to 23: Reserved
A bit value of 1 means Enable the feature.
A bit value of 0 means Disable the feature.
• Email Port Number: 1 register, 2 bytes. This is a 2-byte unsigned integer.
Range: 65535 to 0.
• FTP Port Number: 1 register, 2 bytes. This is a 2-byte unsigned integer.
Range: 65535 to 0.
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
1514131211109876543210
Server / Service Enable
Server / Service Enable