GE EPM 9650/9800 Computer Monitor User Manual


 
6-8
6.6:
Waveform
Trigger
Log
Format
Q
The Waveform Trigger Log stores records in response to High Speed Limit Triggers. It records
descriptive information about records in the Waveform Samples Log.
Q
Record Format: A Record contains 256 Bytes.
The first eight bytes in each record is the Trigger Time Stamp, representing the time of the last
sample of the triggering cycle. The format of the Time Stamp is:
Byte Format Range Description
0 binary 0 – 99 century
1 binary 0 – 99 year
2 binary 1 – 12 month
3 binary 1 – 31 day
4 binary 0 – 23 hour
5 binary 0 – 59 minute
6 binary 0 – 59 second
7 binary 0 – 100 centisecond
Note: This log does not record records during Test Mode.
The next 48 bytes are 12 4-byte MSB signed integers representing the RMS values recorded in
the triggering cycle. The order of these readings is:
V
AN
V
BN
V
CN
V
AUX
I
A
I
B
I
C
I
AUX
I
N
V
AB
V
BC
V
CA
There are currently five hookups available, where the following RMS values are computable in each:
3 Element Wye V
AN
, V
BN
, V
CN
, I
A
, I
B
, I
C
, I
AUX
3 CT Delta I
A
, I
B
, I
C
, I
AUX
, V
AB
, V
BC
, V
CA
2 CT Delta I
A
, I
C
, I
AUX
, V
AB
, V
BC
, V
CA
2-1/2 Element Wye V
AN
, V
CN
, I
A
, I
B
, I
C
, I
AUX
Broken Delta V
AN
, V
BN
, V
CN
, I
A
, I
B
, I
C
, I
AUX
, V
AB
, V
BC
, V
CA