Dimensions and Values
Table 2-2 provides dimensions and their values of HP 9000 rp4410 and rp4440 servers.
Grounding
The site building must provide a safety ground or protective earth for each ac service entrance to all cabinets.
Install a protective earthing (PE) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor is to be connected from the unit to the building installation earth or, if supplied by a separately
derived system, at the supply transformer or motor-generator set grounding point.
PCI Slots Two dedicated for LAN and SCSI; four
64-bit PCI-X slots, 66 MHz, 3.3V slots;
and two 64-bit PCI-X slots, 133 MHz,
3.3V slots.
Two dedicated for LAN and SCSI; four
64-bit PCI-X slots, 66 MHz, 3.3V slots;
and two 64-bit PCI-X slots, 133 MHz,
3.3V slots.
Core I/O Three serial ports, two USB ports,
integrated RJ-45 LAN.
Three serial ports, two USB ports,
integrated RJ-45 LAN.
DVD DVD-R/CD drive, IDE interface, 48x
speed.
DVD-R/CD drive, IDE interface, 48x
speed.
External storage Two external SCSI ports. Two external SCSI ports.
Power supply One power supply standard. A second
power supply (optional) for 1+1
configuration.
One power supply standard. A second
power supply (optional) for 1+1
configuration.
Table 2-2 Server Dimensions and Values
Dimension Value
Height 6.8 in (17.3 cm)
Width 19 in (48.2 cm)
Depth 27.2 in (69.0 cm)
Weight Unloaded 88 lbs (40 kg)
Fully loaded 100 lbs (45.4 kg)
Height 6.8 in (17.3 cm)
Table 2-1 Minimum and Maximum Server Configurations (Continued)
Component rp4410 rp4440