Honeywell UDC2500 Network Card User Manual


 
Input Calibration
138 UDC2500 Universal Digital Controller Product Manual 4/07
PV Input Range Range Values Sensor Type
°F °C 0 % 100 %
S
0 to 3100 –18 to 1704 –0.092 mV 17.998 mV
T
-300 to 700 –184 to 371 –5.341 mV 19.097 mV
T (low)
-200 to 500 –129 to 260 –4.149 mV 12.574 mV
W5W26
0 to 4200 –18 to 2315 –0.234 mV 37.075 mV
W5W26 (low)
0 to 2240 –18 to 1227 –0.234 mV 22.283 mV
RP20-RP40
32 to 3216 0 to 1880 0.000 mV 4.933 mV
Thermocouple
Differential *
–50 to 150 –46 to 66 –1.54 mV 4.62 mV
Honeywell
Radiamatic
Type RH
Type RI **
0 to 3400
0 to 3400
–18 to 1871
–18 to 1871
0.00 mV
0.00 mV
57.12 mV
60.08 mV
RTD
Alpha = 0.00385 per
IEC-60751 (1995)
100 ohms
100 ohms (low)
200 ohms
500 ohms
–300 to 1200
–300 to 300
–300 to 1200
–300 to 1200
–184 to 649
–184 to 149
–184 to 649
–184 to 649
25.202 ohms
25.202 ohms
50.404 ohms
126.012 ohms
329.289 ohms
156.910 ohms
658.578 ohms
1646.445 ohms
Linear
Milliamps
4 to 20 mA
0 to 20 mA
4.00 mA
0.00 mA
20.00 mA
20.00 mA
Millivolts
0 to 10 mV
0 to 50 mV
0 to 100 mV
0.00 mV
0.00 mV
0.00 mV
10.00 mV
50.00 mV
100.00 mV
Volts
1 to 5 Volts
0 to 5 Volts
0 to 10 Volts
1.00 Volts
0.00 Volts
0.00 Volts
5.00 Volts
5.00 Volts
10.00 Volts
* The Factory Calibrated millivolt values for the Thermocouple Differential Input are for a pair
of J thermocouples at an ambient temperature mean of 450°F / 232°C. Other thermocouple
types and ambient temperature means may be accomplished via Field Calibration of the input,
with the range value limits being –4 mV to +16 mV for the zero and span values.
** The range values for Radiamatic Type RI are customer configurable within the limits shown.