Honeywell UDC2500 Network Card User Manual


 
Configuration
38 UDC2500 Universal Digital Controller Product Manual 4/07
Function Prompt
Lower Display
Selection or Range of Setting
Upper Display
English Numeric
Code
English Numeric
Code
Parameter
Definition
read/write.
CAL 1
CALIBRATION—All groups are available for
read/write except for the Calibration and
Keyboard Lockout groups.
CONF 2
+ CONFIGURATION—Tuning, SP Ramp,
and Accutune groups are read/write. All
other groups are read only. Calibration and
Keyboard Lockout groups are not available.
VIEW 3
+ VIEW—Tuning and Setpoint Ramp
parameters are read/write. No other
parameters are viewable.
ALL 4
ALL—Tuning and Setpoint Ramp
parameters are available for read only. No
other parameters are viewable.
AUTOMA 112
DIS
ENAB
0
1
MANUAL/AUTO KEY LOCKOUT—Allows
you to disable the Manual/Auto key.
DISABLE
ENABLE
ATTENTION Can only be viewed if
LOCKOUT is configured for NONE.
RN HLD 114
DIS
ENAB
0
1
RUN/HOLD KEY LOCKOUT—Allows you to
disable the Run/Hold key, for either SP
Ramp or SP Program. The Run/Hold key is
never disabled when used to acknowledge a
latched alarm 1 or a Diagnostic Message.
DISABLE
ENABLE
ATTENTION Can only be viewed if
LOCKOUT is configured for NONE.
SP SEL 115
DIS
ENAB
0
1
SETPOINT SELECT KEY LOCKOUT
Allows you to disable the Setpoint Select
key.
DISABLE
ENABLE
ATTENTION Can only be viewed if
LOCKOUT is configured for NONE.