54 UDC2500 Universal Digital Controller Product Manual 4/07
Function Prompt
Lower Display
Selection or Range of Setting
Upper Display
English Numeric
Code
English Numeric
Code
Parameter
Definition
RLY TYP
MECH
S S
0
1
RELAY CYCLE TIME INCREMENT
selection is used only for Time Simplex and
Duplex output configurations. This
configuration sets the increment size of the
relay cycle times in the Tuning and Tuning 2
Set Up groups.
ELECTROMECHANICAL RELAY—Cycle
time in one-second increments.
SOLID STATE RELAY—Cycle time in 1/3
second increments. This is useful for solid
state relay applications that require shorter
cycle times. DO NOT use this setting unless
cycle times of less than 1 second are
required.
ATTENTION The Lockout selection must
be set to NONE in order to view this
selection.
MTR TI 505
5 to 1800 seconds
MOTOR TIME – Appears only when “TPSC”
(Three Position Step Control) is selected as
the Control Algorithm. This is the time it
takes the motor to travel from 0 to 100 %
(fully closed to fully open). This time can
usually be found on the nameplate of the
motor.