National Instruments 3.21E+04 Computer Hardware User Manual


 
Chapter 4 Signal Connections
National Instruments Corporation 4-19 AT-MIO/AI E Series User Manual
Figure 4-5 summarizes the recommended input configuration for both
types of signal sources.
Figure 4-5. Summary of Analog Input Connections
Input
Differential
(DIFF)
Single-Ended —
Ground
Referenced
(RSE)
Single-Ended —
Nonreferenced
(NRSE)
Floating Signal Source
(Not Connected to Building Ground)
Grounded Signal Source
Examples
• Ungrounded Thermocouples
• Signal conditioning with isolated outputs
• Battery devices
Examples
• Plug-in instruments with
nonisolated outputs
+
-
+
-
V
1
ACH(+)
+
-
+
-
V
1
ACH(+)
ACH (-)
See text for information on bias resistors.
See text for information on bias resistors.
R
Signal Source Type
ACH (-)
AIGND
+
-
+
-
V
1
ACH
AIGND
+
-
+
-
NOT RECOMMENDED
ACH
+ Vg -
V
1
Ground-loop losses, Vg, are added to
measured signal
+
-
+
-
V
1
ACH
AISENSE
R
AIGND
+
-
+
-
V
1
ACH
AISENSE
AIGND
AIGND