Omron C200HE Computer Hardware User Manual


 
19
2. Turn ON the C200HX/HG/HE and switch it to PROGRAM mode.
3. Use a host computer running SSS or a Programming Console to turn ON
SR 27300 (the Save IOM to Cassette Bit). The data will be written from the
PC to the Memory Cassette. SR 27300 will be turned OFF automatically af-
ter the data transfer has been completed.
4. If you want to write-protect the data on the Memory Cassette, turn OFF the
PC and set switch 1 of the Memory Cassette to ON. If this switch is ON, data
in the Memory Cassette will be retained even if SR 27300 is turned ON.
Use the following procedure to read IOM data from a Memory Cassette. The
contents of the error history (DM 6000 through DM 6030) cant be read from the
Memory Cassette.
Note There is no function that automatically reads IOM data from the Memory Cas-
sette.
1, 2, 3... 1. Install the Memory Cassette containing the data into the C200HX/HG/HE.
2. Turn ON the C200HX/HG/HE and switch it to PROGRAM mode.
3. Use a host computer running SSS or a Programming Console to turn ON
SR 27301 (the Load IOM from Cassette Bit). The data will be read from the
Memory Cassette to the PC. SR 27301 will be turned OFF automatically af-
ter the data transfer has been completed.
Reading IOM Data from a
Memory Cassette
Memory Cassettes Section 2-4