489
Limitations Bits in SR 253 through SR 255 can’t be specified.
Only 15 timers/counters or 15 Transition Flags can be set/reset.
The UM settings are not checked when Transition Flags are specified, i.e., as
long as the Transition Flag address does not exceed 1023, the command will be
executed normally even if the specified Flag does not actually exist in the remote
PC.
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
--- OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect. (The forced set/reset/cancel data is 16 bytes long.)
Note With Host Link Units, an error code of 14 (format error) won’t be returned if data
is specified for bit 15 for a timer/counter or Transition Flag. (The forced set/reset/
cancel data can be one byte long or 16 bytes long.)
An end code of 15 (entry number data error) will be returned if the operand, word
address, or bit parameter setting is incorrect. An end code of 15 will also be re-
turned if the a data specification of 0 or 1 is used for a timer or counter Comple-
tion Flag or for a Transition Flag.
An error code of 15 (entry number data error) will be returned if [$C, $D] is speci-
fied for the forced data when set to TC.
End code Contents
00 Normal completion
01 Not executable in RUN mode
13 FCS error
14 Format error
15 Entry number data error
18 Frame length error
10-3-29 FORCED SET/RESET CANCEL –– KC
Cancels all forced set and forced reset bits (including those set by FORCED
SET, FORCED RESET, and MULTIPLE FORCED SET/RESET). If multiple bits
are set, the forced status will be cancelled for all of them.
Command Format
@ KC
x 10
0
x 10
1
↵
Node no. Header
code
TerminatorFCS
Response Format
@ KC
x 10
0
x 10
1
x 16
1
x 16
0
↵
Node no. Header
code
TerminatorFCSEnd code
Host Link Commands
Section 10-3