Omron C200HE Computer Hardware User Manual


 
34
Word(s) FunctionBit(s)
252
00 SEND(90)/RECV(98) Error Flag for operating level 0 of SYSMAC LINK or SYSMAC NET
Link System or CMCR(––) Error Flag for PC Card
01 SEND(90)/RECV(98) Enable Flag for operating level 0 of SYSMAC LINK or SYSMAC NET
Link System or CMCR(––) Enable Flag for PC Card
02 Operating Level 0 Data Link Operating Flag
03 SEND(90)/RECV(98) Error Flag for operating level 1 of SYSMAC LINK or SYSMAC NET
Link System or CMCR(––) Error Flag for PC Card
04 SEND(90)/RECV(98) Enable Flag for operating level 1 of SYSMAC LINK or SYSMAC NET
Link System or CMCR(––) Enable Flag for PC Card
05 Operating Level 1 Data Link Operating Flag
06 Rack-mounting Host Link Unit Level 1 Communications Error Flag
07 Rack-mounting Host Link Unit Level 1 Restart Bit
08 Peripheral Port Restart Bit
09 RS-232C Port Restart Bit
10 PC Setup Clear Bit
11 Forced Status Hold Bit
12 Data Retention Control Bit
13 Rack-mounting Host Link Unit Level 0 Restart Bit
14 Not used.
15 Output OFF Bit
253
00 to 07 FAL number output area (see error information provided elsewhere)
08 Low Battery Flag
09 Cycle Time Error Flag
10 I/O Verification Error Flag
11 Rack-mounting Host Link Unit Level 0 Communications Error Flag
12 Remote I/O Error Flag
13 Always ON Flag
14 Always OFF Flag
15 First Cycle Flag
254
00 1-minute clock pulse bit
01 0.02-second clock pulse bit
02 Negative (N) Flag
03 MTR Execution Flag
04 Overflow Flag (for signed binary calculations)
05 Underflow Flag (for signed binary calculations)
06 Differential Monitor End Flag
07 Step Flag
08 HKY Execution Flag
09 7SEG Execution Flag
10 DSW Execution Flag
11 Interrupt Input Unit Error Flag
12 Reserved by system (not accessible by user)
13 Interrupt Program Error Flag
14 Group-2 Error Flag
15 Special Unit Error Flag (includes Special I/O, PC Link, Host Link, Remote I/O Master Units)
SR (Special Relay) Area Section 3-4