Omron C200HE Computer Hardware User Manual


 
464
10-3-7 AR AREA READ –– RJ
Reads the contents of the specified number of AR words, starting from the speci-
fied word.
Command Format
@ RJ
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
TerminatorBeginning word
(0000 to 0027)
Node no. Header
code
No. of words
(0001 to 0028)
Response Format
@ RJ
FCS
x 10
1
x 10
0
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
Node no. End codeHeader
code
Read data (1 word )
Read data
(for number of words read)
Terminator
Limitations The text portion of the responses first frame can contain up to 30 words.
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
OK OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect and an end code of 15 (entry number data error) will be returned if the
specified words exceed the data area boundaries or arent specified in BCD.
End code Contents
00 Normal completion
13 FCS error
14 Format error
15 Entry number data error
18 Frame length error
10-3-8 EM AREA READ –– RE
Reads the contents of the specified number of EM words, starting from the spe-
cified word in the specified EM bank.
Command Format
@ RE
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
Node no. Header
code
TerminatorBeginning word
(0000 to 6143)
No. of words
(0001 to 6144)
Bank no.
(See note.)
Bank No.
Note Input 00, 01, or 02 to specify bank number 0, 1, or 2. Input two spaces to specify
the current bank.
Host Link Commands
Section 10-3