Omron C200HE Computer Hardware User Manual


 
496
Limitations The registered data is checked from the beginning and the data will be regis-
tered up to any errors. For example, if a command attempts to register 129
items, a frame length error (end code 18) will occur but the first 128 items will be
registered.
DM 6656 to DM 6999 do not exist, but an error will not occur if you try to register
these words.
Bits and words can be specified in any order and they will be registered in the
order that they were specified.
The data can be divided into multiple frames.
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
OK OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK OK OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect or the , data break between two items is omitted.
An end code of 15 (entry number data error) will be returned if the Read area,
Read word address, or Data format setting is incorrect.
End code Contents
00 Normal completion
13 FCS error
14 Format error
15 Entry number data error
18 Frame length error
19 Not executable
A3 Aborted due to FCS error in transmit data
A4 Aborted due to format error in transmit data
A5 Aborted due to entry number data error in transmit data
A8 Aborted due to frame length error in transmit data
10-3-36 COMPOUND COMMAND DATA READ –– QQIR
The bit, word, and timer/counter status is read as a batch according to the read
information that was registered with QQMR.
Command Format
@ QQ
x 10
0
x 10
1
IR
Node no. Header
code
Sub-header
code
TerminatorFCS
Host Link Commands
Section 10-3