Omron C200HE Computer Hardware User Manual


 
491
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect.
End code Contents
00 Normal completion
13 FCS error
14 Format error
18 Frame length error
10-3-31 TEST–– TS
Returns, unaltered, one block of data transmitted from the host computer.
Command Format Specify any characters other than the carriage return (CHR$(13)).
@ TS
x 10
0
x 10
1
Node no. Header
code
Characters
122 characters max.
TerminatorFCS
Response Format The same characters specified in the command will be returned unaltered if the
test is successful.
@ TS
x 10
0
x 10
1
Node no. Header
code
Characters
122 characters max.
TerminatorFCS
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
OK OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 14 (format error) will be returned if a terminator isnt received in
the first frame.
End code Contents
13 FCS error
14 Format error
18 Frame length error
Host Link Commands
Section 10-3