Flags ER: Dd or Dr is not in BCD or when Dr is #0000.
Indirectly addressed DM word is non-existent. (Content of DM word is
not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
Example When IR 00000 is ON with the following program, the content of IR 020 is divided
by the content of HR 09 and the result is placed in DM 0017 and DM 0018. Exam-
ple data and calculations are shown below the program.
DIV(33)
020
HR 09
DM 0017
00000
R: DM 0017 R + 1: DM 0018
11500002
Dd: IR 020
3452
Quotient Remainder
Dd: HR 09
0003
Address Instruction Operands
00000 LD 00000
00001 DIV(33)
020
HR 09
DM 0017
5-19-12 DOUBLE BCD DIVIDE DIVL(57)
Dd: First dividend word (BCD)
IR, SR, AR, DM, HR, TC, LR
Dr: First divisor word (BCD)
IR, SR, AR, DM, HR, TC, LR
Ladder Symbols
Operand Data Areas
R: First result word
IR, SR, AR, DM, HR, LR
DIVL(57)
Dd
Dr
R
@DIVL(57)
Dd
Dr
R
Limitations Dd and Dd+1 must be in the same data area, as must Dr and Dr+1.
R through R+3 must be in the same data area.
Description When the execution condition is OFF, DIVL(57) is not executed. When the
execution condition is ON, DIVL(57) the eight-digit content of Dd and D+1 is di-
vided by the content of Dr and Dr+1 and the result is placed in R to R+3: the quo-
tient in R and R+1, the remainder in R+2 and R+3.
R+1 R
QuotientRemainder
Dd+1 DdDr+1 Dr
R+3 R+2
Flags ER: Dr and Dr+1 contain 0.
Dd, Dd+1, Dr, or Dr+1 is not BCD.
Indirectly addressed DM word is non-existent. (Content of DM word is
not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the result is 0.
BCD Calculations Section 5-19