Omron C200HX Computer Hardware User Manual


 
328
S
R
KEEP(11)
12802
DIFU(13) 12801
@MOV(21)
#000A
DM 0000
12800
00000 25204
12802
12801
@MOV(21)
#0000
DM 0001
@MOV(21)
#0003
DM 0002
XFER(70)
#0010
000
DM 0010
@SEND(90)
DM 0010
DM 0020
DM 0000
00200
XFER(70)
#0016
000
DM 0030
00001 25204
12800
12803
@MOV(21)
#0010
DM 0003
12802
@MOV(21)
#0000
DM 0004
@MOV(21)
#007E
DM 0005
@RECV(98)
HR 10
LR 10
DM 0003
12802 25204
25203
12800 25203
12800 prevents execution of SEND(90) until
RECV(98) (below) has completed. IR 00000
is turned ON to start transmission.
Data is placed into control data words to
specify the 10 words to be transmitted to
node 3 in operating level 1 of network 00
(NSB).
Turns ON to indicate transmission error.
Transmitted data moved into words
beginning at DM 0030 for storage.
12802 prevents execution of RECV(98)
when SEND(90) above has not completed.
IR 00001 is turned ON to start transmission.
Data moved into control data words to
specify the 16 words to be transmitted from
node 126 in operating level 1 of network 00
(NSB).
SEND(90)/RECV(98) Enable Flag
SEND(90)/RECV(98) Error Flag
12800 25204
Resets 12800, above.
DIFU(13) 12803
12802 25204
Resets 12802, above.
00201
12802 25203
Turns ON to indicate reception error.
SEND(90)/RECV(98) Error Flag
S
R
KEEP(11)
12800
Network Instructions Section 5-26