477
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
OK OK OK OK ---
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK --- OK ---
End Codes An end code of 04 (address over) will be returned if the program address is
above the highest program address but less than 65,536 (32,768 in the
C200HS).
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 15 (entry number data error) will be returned if the program ad-
dress exceeds the 65,535 maximum (32,767 in the C200HS), the program ad-
dress isn’t specified in BCD, or the mnemonic/SV operands are incorrect.
An end code of 16 (command not supported) will be returned if the specified
instruction doesn’t exist in the program.
End code Contents
00 Normal completion
04 Address over
13 FCS error
14 Format error
15 Entry number data error
16 Command not supported
18 Frame length error
23 User memory protected
10-3-20 SV CHANGE 1 –– W#
Searches for the first instance of the specified TIM, TIMH(15), CNT, CNTR(12),
or TTIM(87) instruction in the user’s program and changes the SV to new
constant SV specified in the second word of the instruction.
Command Format
@ W#
OP1 OP2 OP3 OP4x 10
0
x 10
1
x 10
3
x 10
2
x 10
0
x 10
1
↵
x 10
3
x 10
2
x 10
0
x 10
1
Node no. Header
code
Mnemonic Timer/counter
(0000 to 0511)
SV (0000 to 9999) TerminatorFCS
Use all four characters to specify the timer or counter instruction’s mnemonic.
Add a space to the end of a TIM or CNT mnemonic to make it 4 characters long.
Instruction name
Mnemonic
TC number
OP1 OP2 OP3 OP4
range
TIMER T I M (Space)
0000 to 0511
HIGH-SPEED TIMER T I M H
COUNTER C N T (Space)
REVERSIBLE COUNTER C N T R
TOTALIZING TIMER T T I M
Host Link Commands
Section 10-3