321
Indirect Destination Beginning Word Designations
D is used to specify the destination beginning word as follows when indirect
specification is designated:
12 to 15 08 to 11 04 to 07 00 to 03
D Area type 0 Word no. (5th
digit)
D+1 Word no. (4th
digit)
Word no. (3rd
digit)
Word no. (2nd
digit)
Word no. (1st
digit)
Indirect designations depend on the series of the destination PC.
CV-series PCs
Addresses in parentheses are for the CV500.
Designation Corresponding CV-series PC words
Area Area
code
Word
number
Area Word number
IR area 00 0 to 999
CIO Area
0 to 999
LR area 06 0 to 63 1000 to 1063
HR area 07 0 to 99 1064 to 1163
SR area 08 0 to 27 1164 to 1191
Timer area (PV) 03 0 to 1023 Timer Area
(PV)
0 to 1023 (0 to 511)
DM area 05 0 to 24575 DM Area 0 to 24575 (0 to 8191)
C-series PCs
Designation
Area Area code Word number
IR area 00 0 to 511
LR area 06 0 to 63
HR area 07 0 to 99
SR area 08 0 to 27
Timer area (PV) 03 0 to 511
DM area 05 0 to 6655
EM area 10 to 17 (Bank 0 to 7)
28 to 2F (Bank 8 to 15)
18 (Current bank)
0 to 6143
Indirect designations depend on the series of the destination PC.
CV-series PCs
Designation
Area Area code Word number
CIO Area 00 0 to 2555
CPU Bus Link Area 01 0 to 255
Auxiliary Area 02 0 to 511
Timer Area 03 0 to 1023
Counter Area 04 0 to 1023
DM Area 05 0 to 24575
EM Area 10 to 17:Bank 0 to 7
18: Current bank
0 to 32765
SYSMAC NET Link Systems
SYSMAC LINK/Ethernet
Systems
Network Instructions Section 5-26