Omron C200HX Computer Hardware User Manual


 
466
Response Format
@ WR
x 10
1
x 10
0
x 16
1
x 16
0
FCSNode no. End codeHeader
code
Terminator
Limitations Data cannot be written to words 253 to 255. If there is an attempt to write to these
words, no error will result, but nothing will be written to these words.
Except for the first word of the write data, the write data can be divided into multi-
ple frames.
PC Settings
PC Mode UM Area
RUN MONITOR PROGRAM Write-protected Read-protected
--- OK OK OK OK
Execution Conditions
Commands Responses
Single Multiple Single Multiple
OK OK OK ---
End Codes An end code of 14 (format error) will be returned if the length of the command is
incorrect or the first word of write data isnt in the first frame.
An end code of 15 (entry number data error) will be returned if the specified write
data exceeds the data area boundaries, the beginning word isnt specified in
BCD, or the write data isnt hexadecimal. (An end code of A5 will be returned
instead of 15 for non-hexadecimal write data in multiple command frames.)
End code Contents
00 Normal completion
01 Not executable in RUN mode
13 FCS error
14 Format error
15 Entry number data error
18 Frame length error
A3 Aborted due to FCS error in transmit data
A4 Aborted due to format error in transmit data
A5 Aborted due to entry number data error in transmit data
A8 Aborted due to frame length error in transmit data
10-3-10 LR AREA WRITE –– WL
Writes data to the LR area, starting from the specified word. Writing is done word
by word.
Command Format
@ WL
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 16
3
x 16
2
x 16
1
x 16
0
Node no. Header
code
TerminatorWrite data (1 word)
Write data
(for number of words to write )
Beginning word
(0000 to 0063)
Host Link Commands
Section 10-3