Schneider Electric 61 Network Router User Manual


 
109
Log parameters
CrPO Parameter name: Channels active on last fault
Logic address: 7290 = 16#1C7A Type: WORD
CANopen index: 202A/5B Read/write: R
INTERBUS index: 5FB9/AA Unit: -
DeviceNet path: 85/01/5B
Command channel: Low order byte:
0: Terminals
2: Graphic display terminal
3: Modbus
6: CANopen
9: Network card
10: "Controller Inside" card
15: PowerSuite
Reference channel: High order byte:
0: Analog input terminals
2: Graphic display terminal
3: Modbus
6: CANopen
7: +/- speed terminals
9: Network card
10: "Controller Inside" card
15: PowerSuite
rtP0 Parameter name: Motor operating time on last fault
Logic address: 7260 = 16#1C5C Type: UINT
CANopen index: 202A/3D Read/write: R
INTERBUS index: 5FB9/8F Unit: 1 hour
DeviceNet path: 85/01/3D
Md0 Parameter name: Date on last fault
Logic address: 7300 = 16#1C84 Type: UINT
CANopen index: 202B/1 Read/write: R
INTERBUS index: 5FB9/B3 Unit: See page 110
DeviceNet path: 85/01/65
This parameter is only significant if a "Controller Inside" card is installed in the drive.
dM0 Parameter name: Time on last fault
Logic address: 7310 = 16#1C8E Type: UINT
CANopen index: 202B/B Read/write: R
INTERBUS index: 5FB9/BC Unit: See page 110
DeviceNet path: 85/01/6F
This parameter is only significant if a "Controller Inside" card is installed in the drive.
Code Description