I/O parameters
Analog inputs
Code Description
AI1C Parameter name: Physical image of analog input 1
Logic address: 5242 = 16#147A Type: INT
CANopen index: 2016/2B Read/write: R
INTERBUS index: 5FB9/36 Unit: 0.001 V
DeviceNet path: 7B/01/2B
AI1r Parameter name: Standardized image of analog input 1
Logic address: 5232 = 16#1470 Type: INT
CANopen index: 2016/21 Read/write: R
INTERBUS index: 5FB9/32 Unit: 1
DeviceNet path: 7B/01/21
AI2C Parameter name: Physical image of analog input 2
Logic address: 5243 = 16#147B Type: INT
CANopen index: 2016/2C Read/write: R
INTERBUS index: 5FB9/37 Unit: 0.001 V or 0.001 mA
DeviceNet path: 7B/01/2C
The unit is:
•0.001 V if parameter [AI2 Type] (AI2t) is configured as [Voltage] (10U)
•0.001 mA if parameter [AI2 Type] (AI2t) is configured as [Current] (0A)
AI2r Parameter name: Standardized image of analog input 2
Logic address: 5233 = 16#1471 Type: INT
CANopen index: 2016/22 Read/write: R
INTERBUS index: 5FB9/33 Unit: 1
DeviceNet path: 7B/01/22
AI3C Parameter name: Physical image of analog input 3
Logic address: 5244 = 16#147C Type: INT
CANopen index: 2016/2D Read/write: R
INTERBUS index: 5FB9/38 Unit: 0.001 mA
DeviceNet path: 7B/01/2D
AI3r Parameter name: Standardized image of analog input 3
Logic address: 5234 = 16#1472 Type: INT
CANopen index: 2016/23 Read/write: R
INTERBUS index: 5FB9/34 Unit: 1
DeviceNet path: 7B/01/23